The minimum available pressure on the consumer. Operation of thermal networks. Water supply scheme with parallel zoning

"Concretization of indicators of the quantity and quality of communal resources in the modern realities of housing and communal services"

SPECIFICATION OF INDICATORS OF QUANTITY AND QUALITY OF UTILITY RESOURCES IN THE MODERN REALITIES OF HUSAL COMPANY

V.U. Kharitonsky, Head of Engineering Systems Department

A. M. Filippov, Deputy Head of the Department of Engineering Systems,

Moscow State Housing Inspectorate

Documents regulating the indicators of the quantity and quality of communal resources supplied to household consumers at the border of responsibility of the resource supply and housing organizations have not been developed to date. In addition to the existing requirements, specialists of the Moscow Housing Inspection propose to specify the values ​​of the parameters of heat and water supply systems at the entrance to the building, in order to maintain the quality of public services in residential multi-apartment buildings.

A review of the current rules and regulations for the technical operation of the housing stock in the field of housing and communal services showed that at present, construction, sanitary norms and rules, GOST R 51617-2000 * "Housing and communal services", "Rules for the provision of public services to citizens", approved by Decree of the Government of the Russian Federation of May 23, 2006 No. 307, and other current regulatory documents consider and set parameters and modes only at the source (central heating station, boiler house, water booster pumping station) that generates a communal resource (cold, hot water and thermal energy), and directly in the apartment of a resident, where a utility service is provided. However, they do not take into account the current realities of the division of housing and communal services into residential buildings and public utility facilities and the established limits of responsibility of the resource supply and housing organizations, which are the subject of endless disputes when determining the guilty party for not providing services to the population or providing services of inadequate quality. Thus, today there is no document regulating the indicators of quantity and quality at the entrance to the house, on the border of the responsibility of the resource supply and housing organizations.

Nevertheless, an analysis of the inspections of the quality of supplied communal resources and services conducted by the Moscow Housing Inspectorate showed that the provisions of federal regulatory legal acts in the field of housing and communal services can be detailed and specified in relation to apartment buildings, which will establish the mutual responsibility of resource-supplying and managing housing organizations. It should be noted that the quality and quantity of utility resources supplied to the boundary of operational responsibility of the resource supplying and managing housing organization, and utility services to residents is determined and evaluated based on the readings, first of all, of common house meters installed at the inputs

systems of heat and water supply to residential buildings, and an automated system for monitoring and accounting for energy consumption.

Thus, Moszhilinspektsiya, based on the interests of residents and many years of practice, in addition to the requirements of regulatory documents and in the development of the provisions of SNiP and SanPin in relation to operating conditions, as well as in order to comply with the quality of public services provided to the population in residential multi-apartment buildings, proposed to regulate on entering heat and water supply systems into the house (at the metering and control unit), the following standard values ​​​​of parameters and modes recorded by common house metering devices and an automated system for monitoring and metering energy consumption:

1) for the central heating system (CH):

The deviation of the average daily temperature of the network water supplied to the heating systems must be within ± 3% of the established temperature schedule. The average daily temperature of the return network water should not exceed the temperature specified by the temperature chart by more than 5%;

The pressure of network water in the return pipeline of the central heating system must be at least 0.05 MPa (0.5 kgf / cm 2) higher than the static one (for the system), but not higher than the permissible one (for pipelines, heaters, fittings and other equipment ). If necessary, it is allowed to install backwater regulators on return pipelines in the ITP of heating systems of residential buildings directly connected to the main heating networks;

The network water pressure in the supply pipeline of the CH systems must be higher than the required water pressure in the return pipelines by the available pressure (to ensure the circulation of the heat carrier in the system);

The available pressure (pressure drop between the supply and return pipelines) of the heat carrier at the input of the central heating heating network into the building must be maintained by heat supply organizations within:

a) with dependent connection (with elevator units) - in accordance with the project, but not less than 0.08 MPa (0.8 kgf / cm 2);

b) with independent connection - in accordance with the project, but not less than 0.03 MPa (0.3 kgf / cm2) more than the hydraulic resistance of the central heating system inside the house.

2) For hot water supply system (DHW):

Hot water temperature in the DHW supply pipeline for closed systems within 55-65 °С, for open heat supply systems within 60-75 °С;

Temperature in the DHW circulation pipeline (for closed and open systems) 46-55 °С;

The arithmetic mean of the temperature of hot water in the supply and circulation pipelines at the inlet of the DHW system must in all cases not be lower than 50 °C;

The available head (pressure drop between the supply and circulation pipelines) at the estimated circulation flow rate of the DHW system must be at least 0.03-0.06 MPa (0.3-0.6 kgf / cm 2);

The water pressure in the supply pipeline of the DHW system must be higher than the water pressure in the circulation pipeline by the amount of available pressure (to ensure the circulation of hot water in the system);

The water pressure in the circulation pipeline of DHW systems must be at least 0.05 MPa (0.5 kgf / cm 2) higher than the static pressure (for the system), but not exceed the static pressure (for the highest located and high-rise building) by more than by 0.20 MPa (2 kgf/cm2).

With these parameters in apartments near sanitary appliances of residential premises, in accordance with the regulatory legal acts of the Russian Federation, the following values ​​\u200b\u200bmust be provided:

Hot water temperature not lower than 50 °С (optimum - 55 °С);

The minimum free pressure at the sanitary appliances of the residential premises of the upper floors is 0.02-0.05 MPa (0.2-0.5 kgf / cm 2);

The maximum free pressure in hot water supply systems near sanitary appliances on the upper floors should not exceed 0.20 MPa (2 kgf / cm 2);

The maximum free pressure in the water supply systems at the sanitary appliances of the lower floors should not exceed 0.45 MPa (4.5 kgf / cm 2).

3) For cold water supply system (CWS):

The water pressure in the supply pipeline of the cold water system must be at least 0.05 MPa (0.5 kgf / cm 2) higher than the static pressure (for the system), but not exceed the static pressure (for the highest located and high-rise building) by more than 0.20 MPa (2 kgf / cm 2).

With this parameter in apartments, in accordance with the regulatory legal acts of the Russian Federation, the following values ​​\u200b\u200bmust be provided:

a) the minimum free pressure at the sanitary appliances of the residential premises of the upper floors is 0.02-0.05 MPa (0.2-0.5 kgf / cm 2);

b) the minimum pressure in front of the gas water heater of the upper floors is at least 0.10 MPa (1 kgf / cm 2);

c) the maximum free pressure in the water supply systems at the sanitary appliances of the lower floors should not exceed 0.45 MPa (4.5 kgf / cm 2).

4) For all systems:

The static pressure at the inlet to the heat and water supply systems should ensure that the pipelines of the central heating, cold water and hot water systems are filled with water, while the static water pressure should not be higher than that allowed for this system.

The water pressure values ​​in the DHW and cold water systems at the inlet of pipelines into the house must be at the same level (achieved by setting the automatic control devices of the heating point and / or pumping station), while the maximum allowable pressure difference should be no more than 0.10 MPa (1 kgf / cm 2).

These parameters at the input to the buildings should be provided by resource supplying organizations by taking measures for automatic regulation, optimization, uniform distribution of heat energy, cold and hot water between consumers, and for return pipelines of systems - also by housing management organizations through inspections, identification and elimination of violations or re-equipment and carrying out adjustment activities of engineering systems of buildings. These measures should be carried out when preparing heating points, pumping stations and intra-quarter networks for seasonal operation, as well as in cases of violations of the specified parameters (indicators of the quantity and quality of communal resources supplied to the border of operational responsibility).

If the specified values ​​of parameters and modes are not observed, the resource supplying organization is obliged to immediately take all necessary measures to restore them. In addition, in case of violation of the specified values ​​of the parameters of the delivered communal resources and the quality of the communal services provided, it is necessary to recalculate the payment for the communal services provided in violation of their quality.

Thus, compliance with these indicators will ensure the comfortable living of citizens, the effective functioning of engineering systems, networks, residential buildings and public utilities that provide heat and water supply to the housing stock, as well as the supply of communal resources in the required quantity and standard quality to the boundaries of the operational responsibility of the resource supply and managing housing organization (at the input of engineering communications into the house).

Literature

1. Rules for the technical operation of thermal power plants.

2. MDK 3-02.2001. Rules for the technical operation of systems and structures of public water supply and sewerage.

3. MDK 4-02.2001. Standard instruction for the technical operation of thermal systems of communal heat supply.

4. MDK 2-03.2003. Rules and norms of technical operation of housing stock.

5. Rules for the provision of public services to citizens.

6. ZhNM-2004/01. Regulations for the preparation for winter operation of heat and water supply systems for residential buildings, equipment, networks and structures of the fuel and energy and public utilities in Moscow.

7. GOST R 51617-2000*. Housing and communal services. General specifications.

8. SNiP 2.04.01-85 (2000). Internal plumbing and sewerage of buildings.

9. SNiP 2.04.05-91 (2000). Heating, ventilation and air conditioning.

10. Methodology for checking the violation of the quantity and quality of services provided to the population in terms of accounting for the consumption of thermal energy, the consumption of cold and hot water in Moscow.

(Energy Saving Magazine No. 4, 2007)

On a piezometric graph, the terrain, the height of the attached buildings, and the pressure in the network are plotted on a scale. Using this graph, it is easy to determine the pressure and available pressure at any point in the network and subscriber systems.

The level 1 - 1 is taken as the horizontal plane of pressure reading (see fig. 6.5). Line P1 - P4 - graph of the pressure of the supply line. Line O1 - O4 - graph of the pressure of the return line. H o1 is the total pressure on the return collector of the source; Hсн - pressure of the network pump; H st is the total head of the make-up pump, or the total static head in the heating network; H to- full pressure in t.K on the discharge pipe of the network pump; D H m is the pressure loss in the heat-preparation plant; H p1 - ​​full pressure on the supply manifold, H n1 = H to - D H t. Available pressure of network water at the CHPP collector H 1 =H p1 - H o1 . Pressure at any point in the network i denoted as H n i , H oi - total pressure in the forward and return pipelines. If the geodetic height at a point i there is Z i , then the piezometric pressure at this point is H p i - Z i , H o i – Z i in the forward and reverse pipelines, respectively. Available pressure at the point i is the difference between the piezometric pressures in the forward and return pipelines - H p i - H oi. The available pressure in the heating network at the subscriber's connection point D is H 4 = H p4 - H o4 .

Fig.6.5. Scheme (a) and piezometric graph (b) of a two-pipe heating network

There is a pressure loss in the supply line in section 1 - 4 . There is a pressure loss in the return line in section 1 - 4 . During operation of the network pump, the pressure H st of the feed pump is regulated by a pressure regulator up to H o1 . When the network pump stops, a static head is set in the network H st, developed by the make-up pump.

In the hydraulic calculation of the steam pipeline, the profile of the steam pipeline can be ignored due to the low steam density. Pressure loss at subscribers, for example , depends on the connection scheme of the subscriber. With elevator mixing D H e \u003d 10 ... 15 m, with elevatorless input - D n be =2…5 m, in the presence of surface heaters D H n = 5…10 m, with pump mixing D H ns = 2…4 m.

Requirements for the pressure regime in the heating network:

At any point in the system, the pressure must not exceed the maximum allowable value. Pipelines of the heat supply system are designed for 16 atm, pipelines of local systems - for a pressure of 6 ... 7 atm;

To avoid air leaks at any point in the system, the pressure must be at least 1.5 atm. In addition, this condition is necessary to prevent pump cavitation;

At any point in the system, the pressure must not be less than the saturation pressure at a given temperature in order to prevent water from boiling.

The operating pressure in the heating system is the most important parameter on which the functioning of the entire network depends. Deviations in one direction or another from the values ​​provided for by the project not only reduce the efficiency of the heating circuit, but also significantly affect the operation of the equipment, and in special cases can even disable it.

Of course, a certain pressure drop in the heating system is due to the principle of its design, namely the pressure difference in the supply and return pipelines. But if there are larger jumps, immediate action should be taken.

  1. static pressure. This component depends on the height of the water column or other coolant in the pipe or container. Static pressure exists even if the working medium is at rest.
  2. dynamic pressure. Represents the force that acts on the internal surfaces of the system during the movement of water or other medium.

Allocate the concept of limiting working pressure. This is the maximum allowable value, the excess of which is fraught with the destruction of individual elements of the network.

What pressure in the system should be considered optimal?

Table of maximum pressure in the heating system.

When designing heating, the coolant pressure in the system is calculated based on the number of storeys of the building, the total length of the pipelines and the number of radiators. As a rule, for private houses and cottages, the optimal values ​​\u200b\u200bof the pressure of the medium in the heating circuit are in the range from 1.5 to 2 atm.

For apartment buildings up to five floors high, connected to a central heating system, the pressure in the network is maintained at a level of 2-4 atm. For nine- and ten-story houses, a pressure of 5-7 atm is considered normal, and in higher buildings - 7-10 atm. The maximum pressure is recorded in the heating mains, through which the coolant is transported from boiler houses to consumers. Here it reaches 12 atm.

For consumers located at different heights and at different distances from the boiler house, the pressure in the network has to be adjusted. Pressure regulators are used to lower it, and pumping stations are used to increase it. However, it should be borne in mind that a faulty regulator can cause an increase in pressure in certain parts of the system. In some cases, when the temperature drops, these devices can completely block the shut-off valves on the supply pipeline coming from the boiler plant.

To avoid such situations, the settings of the regulators are corrected in such a way that complete valve overlap is not possible.

Autonomous heating systems

Expansion tank in an autonomous heating system.

In the absence of centralized heat supply in houses, autonomous heating systems are installed in which the coolant is heated by an individual low-power boiler. If the system communicates with the atmosphere through an expansion tank and the coolant circulates in it due to natural convection, it is called open. If there is no communication with the atmosphere, and the working medium circulates thanks to the pump, the system is called closed. As already mentioned, for the normal functioning of such systems, the water pressure in them should be approximately 1.5-2 atm. Such a low figure is due to the relatively short length of pipelines, as well as a small number of devices and fittings, resulting in a relatively low hydraulic resistance. In addition, due to the small height of such houses, the static pressure in the lower sections of the circuit rarely exceeds 0.5 atm.

At the stage of launching an autonomous system, it is filled with a cold coolant, maintaining a minimum pressure in closed heating systems of 1.5 atm. Do not sound the alarm if, after some time after filling, the pressure in the circuit drops. The pressure loss in this case is due to the release of air from the water, which was dissolved in it when the pipelines were filled. The circuit should be vented and completely filled with coolant, bringing its pressure to 1.5 atm.

After heating the coolant in the heating system, its pressure will increase slightly, while reaching the calculated operating values.

Precautionary measures

A device for measuring pressure.

Since when designing autonomous heating systems, in order to save money, a margin of safety is assumed to be small, even a low pressure jump of up to 3 atm can cause depressurization of individual elements or their connections. In order to smooth out pressure drops due to unstable operation of the pump or changes in the temperature of the coolant, an expansion tank is installed in a closed heating system. Unlike a similar device in an open type system, it does not have communication with the atmosphere. One or more of its walls are made of an elastic material, due to which the tank acts as a damper during pressure surges or water hammer.

The presence of an expansion tank does not always guarantee that the pressure is maintained within optimal limits. In some cases, it may exceed the maximum allowable values:

  • with incorrect selection of the capacity of the expansion tank;
  • in case of malfunction of the circulation pump;
  • when the coolant overheats, which happens as a result of violations in the operation of the boiler automation;
  • due to incomplete opening of shut-off valves after repair or maintenance work;
  • due to the appearance of an air lock (this phenomenon can provoke both an increase in pressure and its fall);
  • with a decrease in the throughput of the mud filter due to its excessive clogging.

Therefore, in order to avoid emergency situations when installing closed-type heating systems, it is mandatory to install a safety valve that will discharge excess coolant if the permissible pressure is exceeded.

What to do if the pressure drops in the heating system

Expansion tank pressure.

During the operation of autonomous heating systems, the most frequent are such emergency situations in which the pressure gradually or sharply decreases. They can be caused by two reasons:

  • depressurization of system elements or their connections;
  • boiler malfunction.

In the first case, the leak should be located and its tightness restored. You can do this in two ways:

  1. Visual inspection. This method is used in cases where the heating circuit is laid in an open way (not to be confused with an open type system), that is, all its pipelines, fittings and devices are in sight. First of all, they carefully examine the floor under pipes and radiators, trying to detect puddles of water or traces of them. In addition, the place of leakage can be fixed by traces of corrosion: characteristic rusty streaks form on radiators or at the joints of system elements in case of leakage.
  2. With the help of special equipment. If a visual inspection of the radiators did not give anything, and the pipes were laid in a hidden way and cannot be inspected, you should seek the help of specialists. They have special equipment that will help detect the leak and fix it if the owner of the house does not have the opportunity to do it himself. Localization of the depressurization point is quite simple: water is drained from the heating circuit (for such cases, a drain valve is cut into the lower point of the circuit at the installation stage), then air is pumped into it using a compressor. The location of the leak is determined by the characteristic sound that the leaking air makes. Before starting the compressor, use shut-off valves to isolate the boiler and radiators.

If the problem area is one of the joints, it is additionally sealed with tow or FUM tape, and then tightened. The broken pipeline is cut out and a new one is welded in its place. Units that cannot be repaired are simply replaced.

If the tightness of pipelines and other elements is beyond doubt, and the pressure in the closed heating system still drops, you should look for the causes of this phenomenon in the boiler. It is not necessary to carry out diagnostics on your own; this is a job for a specialist with the appropriate education. Most often, the following defects are found in the boiler:

The device of the heating system with a manometer.

  • the appearance of microcracks in the heat exchanger due to water hammer;
  • manufacturing defects;
  • failure of the feed valve.

A very common reason why the pressure in the system drops is the wrong selection of the capacity of the expansion tank.

Although the previous section stated that this could cause pressure to rise, there is no contradiction here. When the pressure in the heating system rises, the safety valve is activated. In this case, the coolant is discharged and its volume in the circuit decreases. As a result, over time, the pressure will decrease.

Pressure control

To visually control the pressure in the heating network, dial gauges with a Bredan tube are most often used. Unlike digital instruments, these pressure gauges do not require an electrical connection. Electrocontact sensors are used in automated systems. A three-way valve must be installed on the outlet to the control and measuring device. It allows you to isolate the pressure gauge from the network during maintenance or repair, and is also used to remove an air lock or reset the device to zero.

Instructions and rules governing the operation of heating systems, both autonomous and centralized, recommend installing pressure gauges at such points:

  1. In front of the boiler plant (or boiler) and at its outlet. At this point, the pressure in the boiler is determined.
  2. before and after the circulation pump.
  3. At the entrance of the heating main to a building or structure.
  4. before and after the pressure regulator.
  5. At the inlet and outlet of the coarse filter (sump) to control the level of its contamination.

All measuring and control devices should be regularly verified to confirm the accuracy of their measurements.

Based on the results of the calculation of water supply networks for various modes of water consumption, the parameters of the water tower and pumping units are determined, ensuring the operability of the system, as well as free pressures in all network nodes.

To determine the pressure at the supply points (at the water tower, at the pumping station), it is necessary to know the required pressure of water consumers. As mentioned above, the minimum free pressure in the water supply network of a settlement with a maximum domestic and drinking water intake at the entrance to the building above the ground in a one-story building should be at least 10 m (0.1 MPa), with a larger number of storeys, 4 m.

During the hours of lowest water consumption, the pressure for each floor, starting from the second, is allowed to be 3 m. For individual multi-storey buildings, as well as groups of buildings located in elevated places, local pumping installations are provided. The free pressure at the standpipes must be at least 10 m (0.1 MPa),

In the external network of industrial water pipelines, free pressure is taken according to the technical characteristics of the equipment. The free pressure in the consumer's drinking water supply network should not exceed 60 m, otherwise, for certain areas or buildings, it is necessary to install pressure regulators or zoning the water supply system. During the operation of the water supply system at all points of the network, a free pressure of at least the normative one must be ensured.

Free heads at any point in the network are defined as the difference between the elevations of the piezometric lines and the ground surface. Piezometric marks for all design cases (during household and drinking water consumption, in case of fire, etc.) are calculated based on the provision of standard free pressure at the dictating point. When determining piezometric marks, they are set by the position of the dictating point, i.e., the point with the minimum free pressure.

Typically, the dictate point is located in the most unfavorable conditions both in terms of geodetic elevations (high geodetic elevations) and in terms of distance from the power source (i.e., the sum of head losses from the power source to the dictate point will be the largest). At the dictating point, they are set by a pressure equal to the standard one. If at any point in the network the pressure is less than the normative one, then the position of the dictating point is set incorrectly. In this case, they find the point that has the smallest free pressure, take it as the dictator, and repeat the calculation of the pressures in the network.

The calculation of the water supply system for operation during a fire is carried out on the assumption that it occurs at the highest and most distant points of the territory served by the water supply from the power sources. According to the method of extinguishing a fire, water pipes are of high and low pressure.

As a rule, when designing water supply systems, low-pressure fire-fighting water supply should be taken, with the exception of small settlements (less than 5 thousand people). The installation of a high-pressure fire-fighting water supply system must be economically justified,

In low-pressure water pipes, the pressure increase is carried out only for the duration of the fire extinguishing. The necessary increase in pressure is created by mobile fire pumps, which are brought to the fire site and take water from the water supply network through street hydrants.

According to SNiP, the pressure at any point of the low-pressure fire water pipeline network at the ground level during fire fighting must be at least 10 m. network through leaky joints of soil water.

In addition, a certain supply of pressure in the network is required for the operation of fire pumps in order to overcome significant resistance in the suction lines.

The high-pressure fire extinguishing system (usually adopted at industrial facilities) provides for the supply of water at the fire rate established by the norms of fire and increasing the pressure in the water supply network to a value sufficient to create fire jets directly from hydrants. Free pressure in this case should provide a compact jet height of at least 10 m at full fire water flow and the location of the hose barrel at the level of the highest point of the tallest building and water supply through fire hoses 120 m long:

Nsv pzh \u003d N zd + 10 + ∑h ≈ N zd + 28 (m)

where N zd is the height of the building, m; h - pressure loss in the hose and barrel of the hose, m.

In the high-pressure water supply system, stationary fire pumps are equipped with automatic equipment that ensures that the pumps are started no later than 5 minutes after the fire signal is given. The pipes of the network must be selected taking into account the increase in pressure in the event of a fire. The maximum free pressure in the network of the integrated water supply should not exceed 60 m of the water column (0.6 MPa), and in the hour of a fire - 90 m (0.9 MPa).

With significant differences in the geodetic marks of the object supplied with water, a large length of water supply networks, as well as with a large difference in the values ​​\u200b\u200bof the free pressure required by individual consumers (for example, in microdistricts with different building heights), zoning of the water supply network is arranged. It may be due to both technical and economic considerations.

The division into zones is carried out on the basis of the following conditions: at the highest point of the network, the necessary free pressure must be provided, and at its lower (or initial) point, the pressure must not exceed 60 m (0.6 MPa).

According to the types of zoning, water pipelines come with parallel and sequential zoning. Parallel zoning of the water supply system is used for large ranges of geodetic marks within the city area. For this, lower (I) and upper (II) zones are formed, which are provided with water, respectively, by pumping stations of zones I and II with water supply at different pressures through separate conduits. Zoning is carried out in such a way that at the lower boundary of each zone the pressure does not exceed the permissible limit.

Water supply scheme with parallel zoning

1 - pumping station II lift with two groups of pumps; 2 - pumps II (upper) zone; 3 - pumps of the I (lower) zone; 4 - pressure-regulating tanks

Read also:
  1. Chapter III: Regime applicable to honorary consular officers and consular posts headed by such officers.
  2. MS Access. This field in design view is required to restrict user actions when needed.
  3. A. Programming the operation of a garland operating in the traveling wave mode
  4. Gunn diode oscillators. Constructions, equivalent circuit. Operating modes. Parameters of generators, fields of application.
  5. AUTOMATIC TEMPERATURE CONTROL IN BLOCK GREENHOUSES
  6. Automatic regulation of the robotic cleaning combine 1G405.

In water heat supply systems, consumers are provided with heat by appropriately distributing the estimated flow rates of network water between them. To implement such a distribution, it is necessary to develop the hydraulic regime of the heat supply system.

The purpose of developing the hydraulic regime of the heat supply system is to ensure optimally permissible pressures in all elements of the heat supply system and the necessary available pressures at the nodal points of the heating network, in group and local heating points, sufficient to supply consumers with estimated water consumption. Available pressure is the difference in water pressure in the supply and return pipelines.

For the reliability of the heat supply system, the following conditions are imposed:

Do not exceed the permissible pressures: in heat supply sources and heating networks: 1.6-2.5 MPa - for steam-water network heaters of the PSV type, for steel hot water boilers, steel pipes and fittings; in subscriber units: 1.0 MPa - for sectional hot water heaters; 0.8-1.0 MPa - for steel convectors; 0.6 MPa - for cast iron radiators; 0.8 MPa - for heaters;

Providing excess pressure in all elements of the heat supply system to prevent cavitation of pumps and protect the heat supply system from air leakage. The minimum value of excess pressure is assumed to be 0.05 MPa. For this reason, the piezometric line of the return pipeline in all modes must be located at least 5 m of water above the point of the tallest building. Art.;

At all points in the heating system, pressure must be maintained in excess of the saturated water vapor pressure at the maximum water temperature, ensuring that the water does not boil. As a rule, the danger of boiling water most often occurs in the supply pipelines of the heating network. The minimum pressure in the supply pipelines is taken according to the design temperature of the network water, table 7.1.

Table 7.1



The non-boiling line must be drawn on the graph parallel to the terrain at a height corresponding to the excess head at the maximum coolant temperature.

Graphically, the hydraulic regime is conveniently depicted in the form of a piezometric graph. The piezometric graph is built for two hydraulic regimes: hydrostatic and hydrodynamic.

The purpose of developing a hydrostatic regime is to provide the necessary water pressure in the heat supply system, within acceptable limits. The lower pressure limit should ensure that consumer systems are filled with water and create the necessary minimum pressure to protect the heat supply system from air leakage. The hydrostatic mode is developed with the make-up pumps running and no circulation.

The hydrodynamic regime is developed on the basis of data from the hydraulic calculation of heat networks and is ensured by the simultaneous operation of make-up and network pumps.

The development of the hydraulic regime is reduced to the construction of a piezometric graph that meets all the requirements for the hydraulic regime. Hydraulic modes of water heating networks (piezometric graphs) should be developed for heating and non-heating periods. The piezometric graph allows you to: determine the pressure in the supply and return pipelines; available pressure at any point of the heating network, taking into account the terrain; according to the available pressure and height of buildings, choose consumer connection schemes; select automatic regulators, elevator nozzles, throttle devices for local systems of heat consumers; select mains and make-up pumps.



Building a piezometric graph(Fig. 7.1) is performed as follows:

a) scales are selected along the abscissa and ordinate axes and the terrain and the height of the building of the quarters are plotted. Piezometric graphs are built for main and distribution heating networks. For main heat networks, the scales can be taken: horizontal M g 1: 10000; vertical M at 1:1000; for distribution heating networks: M g 1:1000, M in 1:500; The zero mark of the y-axis (pressure axes) is usually taken as the mark of the lowest point of the heating main or the mark of network pumps.

b) the value of the static head is determined, which ensures the filling of consumer systems and the creation of a minimum excess head. This is the height of the highest building plus 3-5 meters of water.


After applying the terrain and the height of buildings, the static head of the system is determined

H c t \u003d [H zd + (3¸5)], m (7.1)

where N zd is the height of the tallest building, m.

The static head H st is drawn parallel to the abscissa axis, and it should not exceed the maximum operating head for local systems. The value of the maximum working pressure is: for heating systems with steel heaters and for heaters - 80 meters; for heating systems with cast-iron radiators - 60 meters; for independent connection schemes with surface heat exchangers - 100 meters;

c) Then a dynamic regime is built. The suction head of the network pumps Ns is arbitrarily chosen, which should not exceed the static head and provides the necessary head pressure at the inlet to prevent cavitation. The cavitation reserve, depending on the measurement of the pump, is 5-10 m.a.c.;

d) from the conditional pressure line at the suction of the network pumps, the pressure losses on the return pipeline DH arr of the main pipeline of the heating network (line A-B) are sequentially plotted using the results of hydraulic calculation. The magnitude of the pressure in the return line must meet the requirements specified above when constructing a static pressure line;

e) the required available pressure is postponed at the last subscriber DH ab, from the operating conditions of the elevator, heater, mixer and distribution heating networks (line B-C). The value of the available pressure at the point of connection of distribution networks is assumed to be at least 40 m;

e) starting from the last piping node, the pressure losses in the supply pipeline of the main line DH under (line C-D) are postponed. The pressure at all points of the supply pipeline, based on the condition of its mechanical strength, should not exceed 160 m;

g) the pressure loss in the heat source DH um (line D-E) is plotted and the pressure at the outlet of the network pumps is obtained. In the absence of data, the head loss in the communications of the CHP can be taken as 25 - 30 m, and for a district boiler house 8-16 m.

The pressure of network pumps is determined

The pressure of the make-up pumps is determined by the pressure of the static mode.

As a result of such a construction, the initial form of the piezometric graph is obtained, which allows you to evaluate the pressure at all points of the heat supply system (Fig. 7.1).

If they do not meet the requirements, change the position and shape of the piezometric graph:

a) if the pressure line of the return pipeline crosses the height of the building or is less than 3¸5 m away from it, then the piezometric graph should be raised so that the pressure in the return pipeline ensures that the system is filled;

b) if the value of the maximum pressure in the return pipeline exceeds the allowable pressure in the heaters, and it cannot be reduced by shifting the piezometric graph down, then it should be reduced by installing booster pumps in the return pipeline;

c) if the non-boiling line crosses the pressure line in the supply pipeline, then water may boil behind the intersection point. Therefore, the water pressure in this part of the heating network should be increased by moving the piezometric graph upwards, if possible, or installing a booster pump on the supply pipeline;

d) if the maximum pressure in the equipment of the heat treatment plant of the heat source exceeds the permissible value, then booster pumps are installed on the supply pipeline.

Division of the heating network into static zones. A piezometric graph is developed for two modes. Firstly, for a static mode, when there is no water circulation in the heat supply system. It is assumed that the system is filled with water at a temperature of 100°C, thereby eliminating the need to maintain excess pressure in the heat pipes to avoid boiling of the coolant. Secondly, for the hydrodynamic regime - in the presence of coolant circulation in the system.

The development of the schedule begins with a static mode. The location of the full static pressure line on the graph should ensure that all subscribers are connected to the heating network according to a dependent scheme. To do this, the static pressure should not exceed the allowable one from the strength condition of subscriber installations and should ensure that local systems are filled with water. The presence of a common static zone for the entire heat supply system simplifies its operation and increases its reliability. If there is a significant difference in geodetic elevations of the earth, the establishment of a common static zone is impossible for the following reasons.

The lowest position of the static pressure level is determined from the conditions of filling local systems with water and providing at the highest points of the systems of the tallest buildings located in the zone of the largest geodetic marks, an overpressure of at least 0.05 MPa. Such pressure turns out to be unacceptably high for buildings located in that part of the area that has the lowest geodetic marks. Under such conditions, it becomes necessary to divide the heat supply system into two static zones. One zone for a part of the area with low geodetic marks, the other - with high ones.

On fig. 7.2 shows a piezometric graph and a schematic diagram of the heat supply system for an area with a significant difference in geodetic elevations of the ground level (40m). The part of the area adjacent to the source of heat supply has zero geodetic marks, in the peripheral part of the area the marks are 40m. The height of the buildings is 30 and 45m. For the possibility of filling the heating systems of buildings with water III and IV located at the 40m mark and creating an excess head of 5m at the highest points of the systems, the level of the full static head should be located at the 75m mark (line 5 2 - S 2). In this case, the static head will be 35m. However, a head of 75m is unacceptable for buildings I and II located at zero. For them, the permissible highest position of the total static pressure level corresponds to 60m. Thus, under the conditions under consideration, it is impossible to establish a common static zone for the entire heat supply system.

A possible solution is to divide the heat supply system into two zones with different levels of total static pressure - the lower one with a level of 50m (line S t-Si) and the upper one with a level of 75m (line S 2 -S2). With this solution, all consumers can be connected to the heat supply system according to a dependent scheme, since the static pressures in the lower and upper zones are within acceptable limits.

So that when the circulation of water in the system stops, the levels of static pressures are established in accordance with the accepted two zones, a separating device is located at the junction (Fig. 7.2 6 ). This device protects the heating network from increased pressure when the circulation pumps stop, automatically cutting it into two hydraulically independent zones: upper and lower.

When the circulation pumps stop, the pressure drop in the return pipeline of the upper zone is prevented by the pressure regulator “to itself” RDDS (10), which maintains a constant predetermined pressure HRDDS at the point of impulse selection. When the pressure drops, it closes. A pressure drop in the supply line is prevented by a non-return valve (11) installed on it, which also closes. Thus, RDDS and a check valve cut the heating network into two zones. To feed the upper zone, a booster pump (8) is installed, which takes water from the lower zone and delivers it to the upper one. The head developed by the pump is equal to the difference between the hydrostatic heads of the upper and lower zones. The bottom zone is fed by the make-up pump 2 and the make-up controller 3.

Figure 7.2. Heating system divided into two static zones

a - piezometric graph;

b - schematic diagram of the heat supply system; S 1 - S 1 - the line of the total static head of the lower zone;

S 2 - S 2, - line of the total static head of the upper zone;

N p.n1 - pressure developed by the make-up pump of the lower zone; N p.n2 - pressure developed by the make-up pump of the upper zone; N RDDS - head to which the RDDS (10) and RD2 (9) regulators are set; ΔN RDDS - pressure actuated on the valve of the RDDS regulator in hydrodynamic mode; I-IV- subscribers; 1-tank make-up water; 2.3 - make-up pump and bottom zone make-up regulator; 4 - upstream pump; 5 - main steam-water heaters; 6- network pump; 7 - peak hot water boiler; eight , 9 - make-up pump and make-up regulator for the upper zone; 10 - pressure regulator "to yourself" RDDS; 11- check valve

The RDDS regulator is set to the pressure Nrdds (Fig. 7.2a). The feed regulator RD2 is set to the same pressure.

In hydrodynamic mode, the RDDS regulator maintains the pressure at the same level. At the beginning of the network, a make-up pump with a regulator maintains a pressure H O1. The difference between these heads is used to overcome the hydraulic resistance in the return pipeline between the separating device and the circulation pump of the heat source, the rest of the pressure is released in the throttle substation at the RDDS valve. On fig. 8.9, and this part of the pressure is shown by the value of ΔН RDDS. The throttle substation in hydrodynamic mode allows maintaining the pressure in the return line of the upper zone not lower than the accepted level of static pressure S 2 - S 2 .

Piezometric lines corresponding to the hydrodynamic regime are shown in Figs. 7.2a. The highest pressure in the return pipeline at consumer IV is 90-40 = 50m, which is acceptable. The pressure in the return line of the lower zone is also within acceptable limits.

In the supply pipeline, the maximum pressure after the heat source is 160 m, which does not exceed the allowable from the pipe strength condition. The minimum piezometric head in the supply pipeline is 110 m, which ensures that the coolant does not boil over, since at a design temperature of 150 ° C, the minimum allowable pressure is 40 m.

The piezometric graph developed for static and hydrodynamic modes provides the possibility of connecting all subscribers according to a dependent scheme.

Another possible solution for the hydrostatic mode of the heat supply system shown in fig. 7.2 is the connection of a part of subscribers according to an independent scheme. There may be two options here. First option- set the total level of static pressure at 50m (line S 1 - S 1), and connect the buildings located at the upper geodetic marks according to an independent scheme. In this case, the static head in the water-to-water heating heaters of buildings in the upper zone on the side of the heating coolant will be 50-40 = 10 m, and on the side of the heated coolant it will be determined by the height of the buildings. The second option is to set the total level of static pressure at around 75 m (line S 2 - S 2) with the buildings of the upper zone connected according to a dependent scheme, and the buildings of the lower zone - according to an independent one. In this case, the static head in water-to-water heaters on the side of the heating coolant will be 75 m, i.e., less than the permissible value (100 m).

Main 1, 2; 3;

add. 4, 7, 8.