Technical characteristics of pumps wilo tor z40 10. Circulation pumps. Pickup times and times

Wilo TOP-S-40/10-EM is a circulation pump with a power of 0.35 kW, designed for use in heating systems, cold or hot water supply, domestic or industrial air conditioning systems and liquid circulation systems.

Advantages:

Maximum efficiency due to ECM technology

High-efficiency pump especially for cottages and semi-detached houses, as well as for houses with two to six apartments

Integrated motor protection

LED display for setting the setpoint and displaying the current power consumption in watts

Quick electrical connection with Wilo-Connector

Flexible mounting options thanks to compact design

Very high starting torque for safe starting

Key Features:

Pump type: circulation
. Power consumption: 0.35 kW
. Rated power: 0.61 / 0.68 kW
. Throughput: 21 m3/h
. Maximum head: 10 m
. Voltage, V: 1~230
. Water quality: clean
. Maximum working pressure, bar: 10
. Permissible fluid temperature: -20°C to 130°C
. Outlet diameter: 1¼"
. Body material: cast iron
. Degree of protection: IP X4D
. Motor protection: built-in
. Rotor type: wet
. Pump installation: vertical
. Mounting length, mm: 250
. Weight: 15 kg
. Warranty: 1 year
. Country: Germany

  • Delivery in Moscow 500 rubles
  • Delivery within MO: 500 rubles + 50 rubles/km from Moscow Ring Road
  • Delivery in Russia - transport companies
  • Pickup: free

You can always specify a convenient delivery date for you (but not less than two working days) when agreeing on an order. Delivery of goods is carried out from Monday to Friday from 12:00 to 18:00

Delivery at a later or earlier time interval is agreed individually with the Buyer and is carried out for an additional fee.

Delivery on Saturday, Sunday and public holidays (as agreed)

Delivery on weekends and holidays is carried out at the request of the buyer, upon confirmation of the application for 2 working days.

Delivery on weekends and holidays is carried out at the request of the buyer for an additional fee, upon confirmation of the application for 2 working days.

Pickup

You can pick up the order yourself at the pickup point at Podymnaya St., 14 building 37.

Self-delivery of goods is carried out daily except Saturday, Sunday and holidays after confirmation by the sales officer.

Delivery terms

Delivery of orders placed through the Ecolife online store is carried out to the entrance or to the place where a truck can easily drive up and where you can unhinder the unloading of goods, as well as to the points of acceptance of cargo by transport companies transporting to the regions.

The driver of the delivery service can provide the services of a loader only by prior arrangement for an additional fee.

Upon delivery to the Buyer, the seller is responsible for the appearance of the goods until the moment of its acceptance and transfer to the Buyer. Claims for the appearance and configuration of the delivered goods, in accordance with Art. 458 and 459 of the Civil Code of the Russian Federation, it is possible to present only before the transfer of the goods by the Seller to the Buyer. From the moment of acceptance and transfer of the goods, the seller's obligation to transfer the goods is considered fulfilled. The fact of acceptance of the goods by the Buyer is confirmed by the signature in the "Purchase and Sale Agreement" in the column "Acceptance and Transfer Certificate". If the appearance or packaging of the goods do not correspond to the proper quality, the buyer has the right not to accept the goods and not to sign the documents.

Payment

Currently, the Ecolife online store offers the following payment methods for orders:

  • Cash on delivery
    Upon delivery of the order, as well as upon self-receipt of the goods at the pickup point, you can pay for the order in cash at the time of its receipt.
  • Payment by bank transfer
    Payment by details to the company's account upon completion of the receipt in the bank or through the Internet bank. After placing an order, you will receive an invoice for payment and a receipt with our details. The prices indicated on the invoice are final and include VAT. The issued invoice is valid for 5 calendar days. This payment method can be used through any bank operating in Russia.
    Note:
    Banks charge a fee for money transfers. Check with the bank where you plan to pay the receipt for information on the amount of the commission fee. When choosing this payment method, please wait until you receive an invoice.

Glandless circulation pump with threaded or flange connection

Application:

hot water heating systems, industrial circulation systems, air conditioning systems and closed cooling circuits

Product features/benefits:

Used in heating and cooling/air conditioning systems from -20 °C to +130 °C
(TOP-S 80/15 and TOP-S 80/20 from -20 °C to +110 °C)
- Pump housing with cataphoretic coating (KTL) to protect against corrosion in the event of condensation
- Manual power adjustment with 3 speed settings
- Easy installation thanks to PN 6/PN 10 combination flange (for DN 40 - DN 65)

Specifications:

Permissible temperature range -20 °C to +130 °C,
short-term (2 h) up to +140 °C (TOP-S 25/13, 80/15, 80/20 and pumps with Wilo protection module: -20 °C to +110 °C)
- Network connection:
- 1~230V, 50Hz (depending on type)
- 3~230 V, 50 Hz (optional with changeover plug)
- 3~400V, 50Hz
- Protection class IP X4D
- Threaded or flanged connection (depending on type) Rp 1 to DN 100
- Max. operating pressure with standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar)

Equipment/functions
Operating modes:

Switching speed stages

Manual control:

Speed ​​setting: 3 speed steps (2 speed steps for single-phase pumps with P2 ≥ 350 W)

Automatic control:

Full motor protection with integrated electronic shutdown system (standard equipment only for three-phase pumps with P2 ≥ 180 W and single-phase pumps P2 ≥ 350 W, optionally for all types with Wilo?C protection module)

External management:

Control input "Off" priority" (optional for all types with Wilo?C protection module)

Alarm and indication:

Separate/collective fault signaling (floating NC contact) (optional for all types with Wilo?C protection module)
- Collective fault signaling (floating NC contact) (standard equipment only for 3~pumps with P2 ≥ 180 W and 1~ pumps with P2 ≥ 350 W, optional for all types with Wilo-C protection module)
- Separate operation signaling (potential-free NO contact) (optional for all types with Wilo?C protection module)
- Protective winding contact (ESC, potential-free break contact) only for single-phase pumps with P2 = 180 W)
- Fault indicator light (standard equipment only for three-phase pumps with P2 ≥ 180 W and for single-phase pumps with P2 ≥ 350 W, as an option for all types with Wilo-C protection module)
- Indicator lamp for direction of rotation (only for three-phase pumps)

Dual pump control (double pump or two single pumps):

Main/standby operating mode (automatic pump changeover on fault/timer): as an option for all pump types with Wilo-C protection module

Equipment:

For flanged pumps: Flange versions
- Standard version for pumps DN 40 - DN 65: combination flange PN 6/10 (flange PN 16 according to EN 1092-2) for counter flanges PN 6 and PN 16,
- Standard version for DN 80/DN 100 pumps: flange PN 6 (designed PN 16 according to EN 1092-2) for counter flange PN 6,
- Special version for pumps DN 40 - DN 100: flange PN 16 (according to EN 1092-2) for counter flange PN 16,
- Cable entry possible from both sides (only for single-phase and three-phase pumps with P2?180 W)
- Serial equipment of the pumps used in systems of heating, thermal insulation.

Materials:

Pump housing: Gray cast iron
- Impeller: Synthetic material
- Shaft: Stainless steel
- Bearings: metal graphite

Scope of delivery:

Pump
- Thermal insulation
- With seals for threaded connection
- Washers for flange screws (for nominal connection diameters DN 40 ÷ DN 65)
- Instructions for installation and operation

Options:

Special version for operating pressure PN 16 (for a fee)
- Execution for special voltages on request.

Accessories:

Threaded connections for threaded connection
- Compensators
- For 3~400V pumps:
- Switching plug 3~230 V, 50 Hz (not TOP-S 80/15, TOP-S 80/20)
- Wilo C protection module, 3~400 V
- For 1~230 V pumps:
- Disconnect device Wilo SK 602N/SK 622N for complete motor protection
- Wilo C protection module, 1~230 V

Type

Glandless circulation pump with threaded or flange connection

Application

hot water heating systems, industrial circulation systems, air conditioning systems and closed cooling circuits

Designation

Product features/benefits

  • Used in heating and cooling/air conditioning systems from -20 °C to +130 °C (TOP-S 25/13, TOP-S 80/15 and TOP-S 80/20 from -20 °C to +110 °C )
  • Pump housing with cataphoretic coating (KTL) for protection against corrosion due to condensation.
  • Manual power adjustment with
    3 speed steps
  • The pump is easy to install thanks to the combination flange PN 6/PN 10 (for DN 40 - DN 65)

Specifications

  • Permissible temperature range -20 °C to +130 °C,
    short-term (2 h) up to +140 °C (TOP-S 25/13, 80/15, 80/20 and pumps with Wilo protection module: -20 °C to +110 °C)
  • Network connection:
    • 1~230V, 50Hz (depending on type)
    • 3~230 V, 50 Hz (optional with switch plug)
    • 3~400V, 50Hz
  • Protection class IP X4D
  • Threaded or flanged connection (depending on type) Rp 1 to DN 100
  • Max. operating pressure with standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar)

Equipment/functions

Operating modes

  • Switching speed stages

Manual control

  • Speed ​​setting: 3 speed steps (2 speed steps for single-phase pumps with P 2 ≥ 350 W)

Automatic control

  • Full motor protection with integrated electronic shutdown system (standard equipment only for three-phase pumps with P 2 ≥ 180 W and single-phase pumps P 2 ≥ 350 W, optionally for all types with Wilo?C protection module)

External control

  • Control input "Off" priority" (optional for all types with Wilo?C protection module)

Signaling and indication

  • Separate/collective fault signaling (floating NC contact) (optional for all types with Wilo?C protection module)
  • Collective fault signaling (floating NC contact) (standard equipment only for 3~pumps with P 2 ≥ 180 W and 1~ pumps with P 2 ≥ 350 W, optionally for all types with Wilo-C protection module)
  • Separate operation signaling (potential-free NO contact) (optional for all types with Wilo?C protection module)
  • Protective winding contact (SCD, potential-free break contact) only for single-phase pumps with P 2 = 180 W)
  • Fault indicator light (standard equipment only for three-phase pumps with P 2 ≥ 180 W and for single-phase pumps with P 2 ≥ 350 W, as an option for all types with Wilo-C protection module)
  • Direction of rotation indicator lamp (only for three-phase pumps)

Dual pump control (double pump or two single pumps)

  • Main/standby operating mode (automatic pump changeover on fault/timer): as an option for all pump types with Wilo-C protection module

Equipment

  • For flanged pumps: Flange versions
    • Standard version for pumps DN 40 - DN 65: combination flange PN 6/10 (flange PN 16 according to EN 1092-2) for counter flanges PN 6 and PN 16,
    • Standard version for DN 80/DN 100 pumps: flange PN 6 (designed PN 16 according to EN 1092-2) for counter flange PN 6,
    • Special version for pumps DN 40 - DN 100: flange PN 16 (according to EN 1092-2) for counter flange PN 16,
  • Cable entry possible on both sides (only for single-phase and three-phase pumps with P 2 ?180 W)
  • Serial equipment of pumps used in heating systems with thermal insulation.

materials

  • Pump housing: Gray cast iron
  • Impeller: Synthetic material
  • Shaft: Stainless steel
  • Bearings: metal graphite

Scope of delivery

  • Pump
  • thermal insulation
  • With seals for threaded connection
  • Washers for flange screws (for nominal connection diameters DN 40 ÷ DN 65)
  • Installation and operating instructions

Options

  • Special version for operating pressure PN 16 (for a fee)
  • Version for special voltages on request.

Accessories

  • Threaded connections for threaded connection
  • Compensators
  • For 3~400V pumps:
    • Switching plug 3~230 V, 50 Hz (not TOP-S 80/15, TOP-S 80/20)
    • Wilo C protection module, 3~400 V
  • For 1~230V pumps:
    • Disconnect device Wilo SK 602N/SK 622N for complete motor protection
    • Wilo C protection module, 1~230 V

Circulation pump Wilo TOP-S 40/10 DM standard series with flange connection, housing with cataphoretic coating (for corrosion protection), pre-selectable speed levels, indicator lamp for direction of rotation and generalized fault signaling. This pump is used for forced circulation of fluid (water or glycol solution) in heating, air conditioning, cooling, underfloor heating, and hot water systems in private or multi-family buildings.

Wilo TOP-S 40/10 DM is equipped with a wet rotor, which means that the motor is constantly flushed with water and cooled at the same time. This design can significantly reduce the noise characteristics of the pump and the mechanical friction of the rotor. The pump can be controlled both in manual and automatic modes. Manual (setting of speed steps) or automatic control (complete motor protection with integrated electronic shutdown system) is provided.

Technical data of the circulation pump Wilo TOP-S 40/10 DM

vendor code 2165525
Max head
10 m
Bandwidth
20 m3/hour
Connection connector diameter DN40
Rated pressure
PN6/10
Overall length
250 mm
Voltage AC 3*400/230V, 50Hz
Rotation frequency
2200/2500/2800 rpm
Rated motor power
350 W
Power consumption
365/465/585W
Current at 3*400V
0.65/0.82/1.17 A
Current at 3*230V 1.12/1.43/2.02 A
Motor protection
built-in
Minimum inlet pressure at temperatures
liquids 50/95/110/130°C
0,5/5/11/24
Temperature range -20 °C to +130 °C
Permissible fluids
Heating water (according to VDI 2035/VdTÜV Tch 1466)
Water-glycol mixtures, max. the ratio in the mixture is 1:1 (when using mixtures
with glycols, the performance data needs to be adjusted
pump, taking into account the increased viscosity depending on the percentage composition of the mixture)
Type of protection IP X4D
Insulation class H
Housing material Gray cast iron EN-GJL-250
Impeller material
Synthetic material (polypropylene - 50% GF)
Shaft material stainless steel X46Cr13
Bearing material
metal graphite

WILO circulation pump for heating and air conditioning systems

0.00 RUB

Delivery

  1. Delivery in Moscow and the Moscow region is made within 1-2 days from the date of order, by courier or company vehicles. The cost of delivery depends on the destination and urgency, and is specified with the manager. If the delivery coincides with the planned schedule, the delivery is free of charge.
  2. Delivery to the regions of Russia is carried out by carrier companies (Business Lines, Autotrading or any other company at the request of the customer). Delivery cost in accordance with the carrier's tariffs, delivery to the terminal in Moscow is free.

Circulation pump WILO TOP-S 40/10 EM PN6/10 is designed for circulation of coolant in heating systems, air conditioning systems, closed cooling circuits and industrial circulation systems.
Maintenance-free circulation pump WILO TOP-S 40/10 EM PN6/10 with glandless rotor, with flange connections, manual switching of speed stages.

Equipment and functions

– Manual power adjustment with 3 speed levels
– Pumps with 1-phase electric motor: – P2 up to 90 W: built-in winding protection against overheating;

– Pumps with 3-phase electric motor: – P2 up to 90 W: built-in winding protection against overheating;
– P2 ≥ 180 W: Complete motor protection via winding safety contact in combination with tripping device (option: SK 602N/SK 622N)
– Mains connection 3–230 V with optional switching plug

– Cataphoresis-coated pump housing for optimum corrosion protection
– Combination flange PN 6/PN 10 (for DN 40 – DN 65)
- heat-insulating casings.

materials

Pump body: Gray cast iron (EN-GJL-250)
Impeller: Synthetic material (polypropylene - 50% GF)
Pump shaft: Stainless steel (X46Cr13)
Bearings: Metal graphite

Operating parameters

Pumped liquid: Water 100%
Flow rate MAX: 22.7 m3/h
Head MAX: 10.0 m
Fluid temperature: 20 °C
Min. fluid temperature: -20 °C
Max. fluid temperature: 130 °C
Maximum working pressure: 10 bar
Minimum support at
50°C/95°C/110°C: 0.5m/5m/11m

Motor and electronics

Electromagnetic compatibility:
Emitted interference: EN 61000-6-3
Interference immunity: EN 61000-6-2
Mains connection: 1~230V/50Hz
Power consumption P1: 0.12 kW … 0.205 kW
Max. speed: 2150 1/min … 2500 1/min
Current consumption: 0.9 A ... 0.99 A
Degree of protection: IP X4D
Threaded entry for cable: 1×13.5

Mounting dimensions